YAKYFTY-ZP

YAKYFTY-ZP

tds

Code
YAKYFty-zp                             AL/PVC/STA/PVC
Voltage Rating
1.3/3 (3.6) kV
Standards
TS IEC 60502-1
IEC 60228 Conductor
Reaction to Fire Classification ( CPR )
EN 60332-1-2 Flame Retardant
Conductor
Stranded Aluminum Conductor (Class 2)
Insulation
PVC (Polyvinyl Chloride)
Filler
PVC Filler
Armour
Double Steel Tape
Sheath
PVC (Polyvinyl Chloride) UV
Technical Data
Max. Operating Temperature : 80°C
Short  Circuit  Temperature : 170°C (max.5 sec)
Lowest cable installation temperature :  -5°C
Bending Radius : 15D ( D : Overall Diameter )
Test Voltage : 6,5 kV AC or 15,6 kV DC
Application:
For installation indoors and outdoors, in cable ducts, underground , in power or switching stations, local energy distribution
industrial plants, where there is no risk of mechanical damage.
In earth, ducts, on support brackets, in dry and
wet conditions etc., where one does not expect
mechanical damages and the cables are not
exposed to the mechanical tensile strain. In urban
networks, industrial plants, electric power plants
and other electricity consumers and for connection of control devices in industry.
Nominal Cross Section Overall Diameter Net Weight Delivery Length Resistance at 20°C Current Carrying Capacity
(mm²) (mm) (kg/km) (m) (ohm/km) In the Ground at 20°C In the Air at 30°C
1×1000+2×1,5 57,2 5963,5 500 0,0291 – 12,1 796 916
1×1000+2×2,5 57,2 5977,2 500 0,0291 – 7,41 796 916
1×1000+2×4 57,2 5977,7 500 0,0291 – 4,61 796 916
Note 1:
Control core, Copper conductor with PVC insulation.
Note 2:
Current carrying capacities are valid at 30°C ambient temperature.
Scroll to Top