NYIFY-R

NYIFY-R

tds

Code
NYIFY-R      CU/PVC/PVC
Voltage Rating
300/500 V
Standards
VDE 0250 Teil 201
IEC 60228 Conductor
Reaction to Fire Classification ( CPR )
EN 60332-1-2 Flame Retardant
Conductor
Stranded Copper Conductor (Class 2)
Insulation
PVC (Polyvinyl Chloride)
Filler
Armour
Sheath
PVC (Polyvinyl Chloride)
Technical Data
Max. Operating Temperature : 70°C
Short  Circuit  Temperature : 160°C (max.5 sec)
Bending Radius : 12D ( D : Overall Diameter )
Test Voltage : 2 kV
Application
Suitable for dry and humid areas. All type of factory , warehouse and depots where there is fire and explosion threat. Not suitable for
underground. Used in fixed installations laying in conduit and under plaster.
Nominal Cross Section Overall Diameter Net Weight Delivery Length Resistance at 20°C Current Carrying Capacity
(mm²) (mm) (kg/km) (m) (ohm/km) In Ground at 20°C In Air at 30°C
2×1,5 13,3 x 4,1 80,5 1000 12,1 19
2×2,5 14,2 x 4,6 103,5 1000 7,41 27
2×4 16,0 x 5,5 146,7 1000 4,61 34
2×6 17,1 x 6,1 191,5 1000 3,08
Nominal Cross Section Overall Diameter Net Weight Delivery Length Resistance at 20°C Current Carrying Capacity
(mm²) (mm) (kg/km) (m) (ohm/km) In Ground at 20°C In Air at 30°C
3×1,5 18,2 x 4,1 112,6 1000 12,1 19
3×2,5 20,4 x 4,5 151,5 1000 7,41 27
3×4 23,3 x 5,5 213,0 1000 4,61 34
3×6 25,4 x 6,3 289,7 1000 3,08
Note :
Current carrying capacities are valid at 30°C ambient temperature