A05Z1-AK / A07Z1-AK

A05Z1-AK / A07Z1-AK

tds

Code :
A05Z1-AK , A07Z1-AK                     AL/HFFR
Voltage Rating:
300/500 V , 450/750 V
Standards :
IEC 60228 Conductor (Special Values)
EN 61034 Low Smoke Density
EN 50267-2-1 and 2-3 Halogen Free
IEC 60754-1 and -2 Halogen Acid Gas Indication
CE Conformity Declaration – All our Cables
Reaction to Fire Classification ( CPR )
EN 60332-1-2 Flame Retardant
Conductor:
Flexible Aluminum Conductor (Class 5)
Insulation:
HFFR
Filler
Armour
Sheath
Technical Data
Max. Operating Temperature :  – 40ºC to +90ºC
Short  Circuit  Temperature : 160°C (max.5 sec.)
Bending Radius : 6D ( D : Overall Diameter )
Test Voltage : 2 kV – 2,5 kV
Application:
Used  in energy networks in refineries, mines, hotels, schools, tunnels, high constructions, hospitals,
power plant, data processing centers, business center where there is a risk of fire.
Nominal Cross Section Overall Diameter Net Weight Delivery Length Resistance at 20°C Current Carrying Capacity
(mm²) (mm) (kg/km) (m) (ohm/km) AL -Conduit AL – Air
1×0,50*   ** 2,1 6,7 100 56,14
1×0,75*   ** 2,3 7,5 100 37,43
1×1*    ** 2,5 9,4 100 28,07
1×1,5** 2,9 12,9 100 19,25 11 18
1×2,5** 3,6 19,2 100 11,55 15 24
1×4** 4,2 26,1 100 7,22 20 32
1×6** 4,7 33,6 100 4,81 26 41
1×10 6,2 55,3 100 3,08 35 55
1×16 7,0 74,6 100 1,91 46 74
1×25 9,1 117,6 1000 1,20 60 97
1×35 10,1 149,1 1000 0,868 74 119
1×50 11,5 200,6 1000 0,641 89 149
1×70 13,3 271,1 1000 0,443 113 184
1×95 15,6 366,0 1000 0,320 137 219
1×120 17,3 444,6 1000 0,253 158 258
1×150 19,0 555,8 1000 0,206 180 293
1×185 21,3 682,8 1000 0,164 205 336
1×240 24,3 899,8 1000 0,125 241 396
1×300 26,9 1107,9 1000 0,100
1×400 30,4 1421,9 1000 0,0778
1×500 34,6 1771,3 1000 0,0605
1×630 37,9 2191,9 1000 0,0469
Note 1:
* For A05Z1-AK Cables
Note 2:
* Conductor resistance calculated theoretically.Conductor resistances are taken from EN 60228 Class-2 Aluminum values.
Note 3:
Current carrying capacities are valid at 30°C ambient temperature.
Scroll to Top